Mines safety alert no. 308 | 12 August 2014 | Version 1

Arc flash and blast when 1000V circuit breaker reset

What happened?

An electrician was resetting a 400A 1000V circuit breaker in a low voltage switchboard on a mine's underground 11kV/1000V substation, when an arc flash and blast left him with serious burns.

Recommendations

  1. Ensure enclosures are fit for purpose and an arc flash assessment is taken into account when determining that risks are at acceptable levels.
  2. Install any arc barriers provided by the circuit breaker manufacturer.
  3. Ensure circuit breaker cable connections are adequately insulated with materials appropriate for the environment and application.
  4. Regular maintenance and inspection of substations and switchboards at the mine must effectively monitor the safety of the electrical installation and its protective features (For example, protection settings, exposed live parts and contamination).
  5. Avoid standing in front of circuit breakers and switches on switchboards when operating them, to avoid the potential projection of arc flashes or blasts.
  6. Wear fit for purpose personal protective equipment during electrical switching activities.
  7. Maintenance personnel must be competent and aware of the safety procedures when performing electrical work in substations and switchboards.
  8. See relevant safety alerts and bulletins, including:

Investigations are ongoing and further information may be published as it becomes available. The information in this publication is what is known at the time of writing.

We issue Safety Notices to draw attention to the occurrence of a serious incident, raise awareness of risks, and prompt assessment of your existing controls.

Comments

The investigation found the following:

Authorised by Hermann Fasching - Manager, Safety and Health

Contact:

Issued by Queensland Department of Natural Resources and Mines

Placement: Place this announcement on noticeboards and ensure all relevant people in your organisation receive a copy.